Building a DOL motor starter panel: the five parts and what sizes each
Direct-on-line is still the right answer for most cage induction motors. The isolator, the short-circuit protection, the contactor, the overload and the control circuit — what each is chosen on, why the contactor comes from the AC-3 column, and why type 2 coordination decides that they all come from one range.
On this page
A direct-on-line starter is the simplest way to run a three-phase cage induction motor, and it is still the right answer for most of them. It is also the assembly most often specified from memory, one part at a time, with a contactor sized off the wrong current figure and an overload set to the top of its band. This is what actually goes in the panel, in the order the decisions have to be made.
What a DOL starter is, and when it is not enough
Direct-on-line means the full supply voltage is applied to the motor’s terminals at the moment of starting. The motor draws its locked-rotor current — for a standard cage motor, several times full-load current — until it accelerates, and produces a correspondingly large starting torque. It is mechanically and electrically the simplest arrangement: no transition, no timing, nothing to commission beyond setting the overload.
Two things push a design away from DOL. The first is the supply: the utility or the site’s own transformer may limit the starting current permitted on a given feeder, and in South Africa the local supply authority’s requirements are the binding constraint, not a rule of thumb. The second is the driven machine: a load that cannot tolerate the torque step — a belt conveyor that will slip, a pump that will hammer the column — needs a soft starter or a drive regardless of what the supply would allow. Where either applies, the assembly changes; the star-delta, soft-start and variable-speed alternatives each carry their own component list.
The five parts, and what selects each
- An isolator or main switch-disconnector — so the panel can be made safe for work. Its rating is a current and a utilisation category, and for motor circuits AC-23 is the category that describes switching a motor load.
- Short-circuit protection — a motor-rated circuit breaker, a motor protection circuit breaker, or fuses. Its job is the fault, not the overload. The prospective fault current at the board decides its breaking capacity, and that figure comes from the installation, not from the motor.
- A contactor — sized on its AC-3 rating at your supply voltage, because AC-3 is the utilisation category that describes starting a cage motor and switching it off while it runs. Manufacturers publish an AC-3 motor rating in kW at 400 V for each frame; that is the figure to match against the nameplate.
- An overload relay — thermal or electronic, with a setting range that contains the motor’s full-load current, set to that current. It protects the winding against a sustained overload and, on a three-phase relay, against single-phasing.
- Control — start and stop, a holding contact or a control relay, and whatever interlocks the process needs. This circuit is where IEC 60947-5-1 devices belong, and it is worth drawing before it is wired.
Sizing the contactor and the overload
The contactor comes from the kW figure and the overload from the amp figure, and they are two independent lookups against two different published ratings. The motor starter selector on this site does exactly that: enter the two nameplate numbers and it lists the order codes whose own published AC-3 rating covers the motor, and the overload relays whose printed setting range contains the current. It converts nothing.
Two judgements remain yours. The first is the coil voltage — the same contactor frame is stocked with 24 V DC, 110 V AC, 230 V AC and wide-range coils, and the choice belongs to the control circuit, not to the motor. The second is whether to take one frame up. A high starting frequency, a long or hot cable run, an ambient well above the reference temperature or a duty that will drift towards AC-4 are all reasons to; the manufacturer’s own derating tables for the frame are where that question is answered.
Coordination: the part that is easy to skip
The breaker, contactor and overload relay are not three independent choices. IEC 60947-4-1 defines type 1 and type 2 coordination to describe what may happen to the assembly when a short circuit occurs downstream of it. Under type 1 the contactor and relay may be damaged, provided the damage stays inside the enclosure; under type 2 the assembly must be fit for further service, with no more than light contact welding that can be separated.
Which combinations achieve which is not something to reason out: every manufacturer publishes coordination tables naming the exact breaker, contactor and relay together, at a stated prospective fault current and voltage. A panel specified to type 2 must be built from a combination that appears in one of those tables. Mixing manufacturers across the three devices leaves you with no table to cite, which is the practical reason motor starter assemblies are usually kept within one range.
The rest of the enclosure
The parts above are the circuit. The panel also needs an enclosure with an IP rating suited to where it will hang and a size that respects the manufacturers’ clearances; DIN rail, ducting, and terminals rated for the conductor sizes actually landing in them; correct labelling and a durable circuit diagram; and, if the ambient or the dissipated heat demands it, climate control. Heat is the item most often left out of a first cut: the losses of the devices inside a sealed enclosure in the sun are a real thermal load, and every manufacturer publishes a power-loss figure per device for exactly this calculation.
Before you order
- Read both nameplate figures rather than deriving one from the other.
- Size the contactor from the AC-3 column at your voltage, never AC-1.
- Choose an overload whose range contains the full-load current, and set it to that current — not to the top of the band.
- Take breaker, contactor and relay from one manufacturer’s coordination table, and record the coordination type on the drawing.
- Confirm the coil voltage against the control circuit, not the power circuit.
- Check the enclosure’s IP rating against the environment and its thermal load against the sum of the device losses.